Instruction manual
Transkript
Instruction manual
Please keep next to the MVHR unit! maxi 801 DC maxi 1201 DC maxi 2001 DC maxi 3001 DC maxi 4001 DC Operating Instructions Mechanical Ventilation Heat Recovery Unit pict.: maxi 2001 Status: 09.09 pict.: Remote control ® WÄRMERÜCKGEWINNUNG Paul Wärmerückgewinnung GmbH August-Horch-Straße 7 08141 Reinsdorf Deutschland Tel.: +49(0)375 - 303505 - 0 Fax: +49(0)375 - 303505 - 55 TABLE OF CONTENTS Seite 0. INTRODUCTION....................................................................................................................... 1 I. GENERAL MAINTENANCE...................................................................................................... 1 II. INSTALLATION........................................................................................................................ 3 2.1. How to assemble the roof (VEX option)................................................................................ 2.2 Connecting the drain pan.….........................……………………………………………...……. 2.3 Other installation advices.........................……………………………………………………….. III. WIRING INSTRUCTIONS ….....……………..…………………………………………….......…... 3 4 5 5 3.1 General informations.............................................................................................................. 3.1.1 General schematic of the Maxi units……………………………......………..…………..... 3.1.2 Schematic of the T° sensors positioning in the Maxi unit............................................... 3.1.3 Label placed in the box 3 cover (i/o REC print board)............……………..…………..... 3.2 Power supply to the fans and the control devices…............................……………..………… 3.3 Power supply for the electric antifreeze coil KWin (option)................................…...……….. 3.4 Power supply and connections for the electrical post heating coil KWout (option)............... 3.4.1 Power supply…...............................……………………………………………..…………. 3.4.2 Coil Control………………………………………………..…..................................………. 3.5 Connecting the post heating water coil (option)..........………..........................................….. 3.5.1 Power supply…………………………………………..............................……..………..…. 3.5.2 Water connection (to be made by the installer)………...............……………..……….…. 3.6 Starting the TAC3 Maxi control.............................................................................................. 3.6.1 General schematic of the Maxi control device……………………….........………….....…. 3.6.2 Connecting the remote control to the i/o REC module…..............…………………...…… 3.6.2.1 Open the RC casing...................................................................................................... 3.6.2.2 Wiring diagram to connect the RC module to the i/o REC module............................... 3.6.3 Selecting the Master…......................................................................……………...……... IV. SYSTEM CONFIGURATION INSTRUCTIONS...................................…………...……............ 5 5 6 6 6 7 7 7 7 8 8 9 10 10 10 11 12 12 14 4.1 Working modes…......................................……………………………………..….……............ 4.1.1 CA Mode: setup, operating instructions and wiring diagrams......................................... 4.1.1.1 Setup CA mode............................................................................................................ 4.1.1.2 Operating CA mode with RC module master............................................................... 4.1.1.3 Operating CA mode with i/o module master................................................................ 4.1.2 LS Mode : setup, operating instructions and wiring diagrams......................................... 4.1.2.1 Setup LS mode............................................................................................................ 4.1.2.2 Operating LS mode with RC module master................................................................ 4.1.2.3 Operating LS mode with i/o module master................................................................. 4.1.3 CPs Mode : setup, operating instructions and wiring diagrams...................................... 4.1.3.1 Setup CPs mode.......................................................................................................... 4.1.3.2 Operating CPs mode with RC master.......................................................................... 4.1.3.3 Operating CPs with i/o module master......................................................................... 4.2 Bypass control with Maxi’s TAC3 Maxi control................................…………...……………... 4.3 Standard built in antifreeze protection of the heat exchanger................................………..... 4.4 Antifreeze the heat exchanger with pre-heating KWin (option).............................................. 4.4.1 Setup of the KWin pre-heating coil control..........................................................……..... 4.4.2 Modifying the assigned floor T°…..............................................…....………….………... 4.4.3 Control features of the TAC3 Maxi……........................................................................... 4.5 KWout post heating electrical coil control (option)…........................................................….. 4.5.1 Setup of the KWout post-heating coil control ….....…...............................................….. 4.5.2 Modification of the assigned floor T° (caution: maximum 50°C)…........………………… 4.5.3 Control features of the TAC3 Maxi.…….................................………………….………... 4.6 NV post heating of the supply air with a water coil (option)................................................… 4.7 Working with CT option …………………………….......................................…………………. 4.8 Display on the RC.......………………………...............................................................………. 4.9 Fan failure alarm…............................................…………………………….……..……………. 4.10 Actual airflow / pressure output signals.….…………...........................................………….. 4.11 Advanced setup…………………………………....................................................……..…… 14 15 15 16 16 18 18 19 20 21 21 22 22 23 24 24 25 25 25 26 27 27 28 28 28 28 29 30 30 Fortsetzung Folgeseite 4.12 Alarms………………….……………………………………..............…………………...……… 4.12.1 Alarm types……………..……………………………………..........................…...……..... 4.12.2 Alarm table......……………...….................….………………………………….………..... 4.12.3 Wiring diagram of relays when alarms.......................................................................... 4.13 Fire alarm………………………………..................................……………………….………… 4.13.1 Configuration……..……………………….....................................………………...…….. 4.13.2 Wiring diagram of fire alarm.………………...........................………………….………... 31 31 33 34 34 34 34 Anhänge Appendix 1: ADVANCED SETUP...................................................................................................................... Appendix 2: TECHNICAL INFORMATION - RC TAC3 - ALARMS............................................................….. Appendix 3: TECHNICAL DOCUMENTATION VISUALIZATION..................................................................... Appendix 4: INSTALLATION INSTRUCTIONS NV POSTHEATING COIL...................................................... Appendix 5: INSTALLATION CONTROL DATASHEET................................................................................... 35 38 47 50 55 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 0. INTRODUCTION PLEASE READ THIS MANUAL CAREFULLY BEFORE START-UP! This manual contains all the required instructions for an optimal assembly of a unit and the heat recovery device (WRG) of the type . It also serves as a guide for maintenance and customer service work. Using this manual, you can learn how to easily use your heat recovery device in as optimal a way as possible. In case you have to do any work inside the device we recommend taking the advice of the installation company. The device is subjected to continuous improvement and further development. It is possible, therefore, that your device differs slightly from the description. We hope you enjoy using your . PLEASE NOTE: Great care has been taken in preparing this manual. However, you are not entitled to any rights through its use. We reserve the right to modify the content of this manual, partially or completely, at any time. I. GENERAL MAINTENANCE INSTRUCTIONS CONSTRUCTION characteristics The structure is made out of omega shaped anodized aluminum profiles connected by reinforced polypropylene auto-extinguishable (M1) corner pieces. The panels are 30mm double skin steel plates insulated. The outside panels are 0,8mm thick pre-painted (5µm primer + 20µm polyester)-gray RAL 9002 color, covered with a plastic protection (to be removed after installation). The inside panel is 0,8mm galvanized steel. This combination allows the exposure of the panels to outdoors conditions, and forms a rigid structure. Thermal insulation is carried out by EPS panels (density 30 g/l), self-extinguishing (M1 class), in conformity with the European environment standards, inserted between layers. The is mounted on a steel frame and is mono-structured. All the access doors to the ventilators and filters are equipped with handles. Air tightness: Internal: Class 1 as per EN 13141-7. External: Class 2 as per EN 13141-7. TAC technology fans The series is equipped with TAC technology centrifugal ventilators. The regulation TAC3 is specifically developed to take advantage of this technology. Verify that the supplied voltage corresponds to the specification of the ventilators and that the connection is made according to the supplied wiring instructions. Attention! : The starting up / stop of the unit must be activated by using the softstop function on K1/K2/K3 or via the RC, and not by shutting off the power supply. Always check the following electrical specifications: Power supply voltage: 230VAC (210V<V<250V). Power supply frequency: 50/60 Hz. Grounding the unit is compulsory The motor is self-protected against overloading. It is thus NOT necessary to install an electrical overload protection device. See section 3.2 for detailed wiring instructions. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 1 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Before starting the unit - If the fan wheel is turning properly, without resistance? - Verify if the installation and the connections are made according to the applicable European standards. - Are the precautionary measures to avoid an accident taken? (Wiring, rotating parts, security measures,) Operating conditions The temperature over the fan motor cannot be lower than -10°C, or superior to 55°C. The unit is not designed to operate in an aggressive or an explosive environment. It is strongly not advised to stop and start the unit more often than every 5 minutes. About the counterflow AIR/AIR heat exchanger When properly maintained the heat exchanger will obtain efficiencies superior to 90% according to working conditions. This may result in the production of condensates which will be collected by the drain pan. In severely cold conditions, condensation can also cause a production of frost on the heat exchanger. Before starting the unit, check that the drain pan is properly connected with the siphon delivered, and that the connections to the drainage are airtight. The slope of the drainage must be of at least of 1cm/m. The siphon must be accessible In the outdoor version of the a siphon with membrane is supplied If a risk of frosting of the drainage is existent, install a wire resistance (not supplied). Protect the heat exchanger by regularly cleaning or replacing the filters. To protect from frosting, the TAC3 control is as standard delivered with an inbuilt heat exchanger antifreeze system (by unbalancing the in and out airflows). There is also the KWin pre-heater option available to accomplish this if deemed necessary. The units are specified not to exceed a frontal air speed on the heat exchanger of 2,2m/s. Fan maintenance Before proceeding to maintenance, first stop the fans using the softstop feature and the only then proceed to the shutdown of the power supply. Verify the state of the fans. If they need to be cleaned use dry or moist cloths with a degreaser. Be careful not to alter the balancing of the fans when doing this. Do not remove the clips of balancing). Filters units are delivered with G4 filters for the air ‘out’ flow and F7 filters for the air ‘in’ flow. Filters are the protectors of the heat exchanger, but also of the quality of the air you breathe. Check regularly (once a month) the state of the filters. Vacuum the filters if necessary, and replace them when they are too dirty. Clogged filters can create the following failures: - Insufficient ventilation - Excessive increase of the rotation speed of the fan creating excessive noise and power consumption - A damaged filter allows 'dirty' air to enter the heat exchanger which will eventually clog the heat exchanger Filter identification for replacement: Unit type Filter(s) air “out” 801 1 x G4 (470x287x50) – cid 125054 1201 1 x G4 (830x287x50) – cid 125055 2001 2 x G4 (503x370x50) – cid 125063 3001 1 x G4 (503x370x50) – cid 125063 2 x G4 (436x370x50) – cid 125065 4001 4 x G4 (436x370x50) – cid 125065 Filter(s) air “in” 1 x F7 (470x287x50) – cid 125056 1 x F7 (830x287x50) – cid 125057 2 x F7 (503x370x50) – cid 125062 1 x F7 (503x370x50) – cid 125062 2 x F7 (436x370x50) – cid 125064 4 x F7 (436x370x50) – cid 125064 © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 2 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Installation control datasheet (see appendix) When the installation is completed and running, we strongly advise that the installer fills in the installation datasheet recapitulating all the data useful for maintenance of the installation. Please keep a copy of this datasheet closely as it may come handy for many reasons: • make a clear communication in case of discussion with the manufacturer • information if you need to change parameters when necessary, • this document can become an important factor in case of guarantee issues. Guarantee The guarantee of the manufacturer begins at the date of invoicing of PLC to the installer. The guarantee is of 2 years, except on the mobile parts where it is of 1 year. The guarantee is limited to the replacement of the defective parts, and does not include labor and traveling expenses. The guarantee becomes void if: • The installation is not accomplished according to the prescriptions described in this above. • Repairs were carried out by unqualified staff. • The startup control datasheet (see appendix) is not filled in properly and not made available when claiming Conformity CE, under formal condition that the final product integration is made in conformity with the applicable standards. II. INSTALLATION INSTRUCTIONS 2.1. How to assemble the roof (VEX option) The roof (VEX) option is delivered unassembled for transportation reasons. Please follow these instructions to assemble the different parts: a) Remove the plastic film from the top part of the unit. Make a silicone seal (not supplied) between the panels and between the aluminum profiles on the top part of the unit, as shown on the picture a) b) Place the different elements of the roof on top of the unit, over the silicone seals. Make sure you leave an adequate distance on each side of the unit so as to cover the whole unit properly. (Suggested distance: +/-50mm on the sides, and +/-100mm on the front and back of the ). a) b) c) Use the supplied M8 screws to screw the roof onto the unit. The screws must be screwed into the aluminum profile and properly aligned. Use a pen to point the location of the screw. Mount the plastic caps supplied over the screw heads. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 3 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG d) Insert silicone inside the U-clip used to join the different roof parts and place the clip over the roof sections as shown on picture d1 and d2. c) d1) e) Make a silicone seal between the aluminum profile and the roof all around the unit, as shown in picture e). d2) e) 2.2 Connecting the drain pan • If the unit is installed indoors: Before starting, control the following points: - if the drain pan is watertight; - the connection between the drain pan and the evacuation pipe is airtight; - the height of the siphon is at least of 120 mm; - the pressure difference between outside and inside the unit cannot exceed 350 Pa; indoor siphon - check for the presence of a ventilation downstream of the siphon; - the slope of the evacuation pipes is at least 1 cm/m; - the siphon is accessible to allow cleaning • If the is installed outdoors: The siphon delivered with for outdoor application is a special siphon with a membrane. It is thus not necessary to fit it to a drainage pipe as the water can directly drop on the ground. The membrane integrated into this type of siphon creates the air tightness. outdoor siphon © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 4 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG 2.3 Other installation advices z Make sure the unit is installed on a flat surface z Leave sufficient access to the unit. Make sure it is possible to access to all the components for maintenance: fans, controls and filters. We advise at least 50 cm on each sides of the unit, z Special care has been taken to deliver an airtight unit. Make sure the ductwork is also very airtight, specially at the connections with the unit on the supply air side. z If the unit is installed outdoors, take the dominating winds into account when orientating the unit. Try to protect the air inlet as much as possible from storm winds and rain. III. WIRING INSTRUCTIONS 3.1 General informations 3.1.1 General schematic of the units 8 4 9 7 1 2 3 5 6 10 1. Main switch for power supply to fans and control 2. Main switch for power supply to pre (Kwin) and/or post (Kwout) heating coils 3. Controls for KWin and/or KWout (options) and i/o REC circuit (i/o module) 4. Central wiring station CBr4 TAC3 REC (factory pre-wired) 5. By-pass 100% 6. Drain pan and connection pipe 7. Supply Fan 8. Exhaust fan 9. Air/Air heat exchanger 10. Remote Control (RC) © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 5 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG All electrical connections made the installer are in 1/2/3/10. 3.1.2 Schematic of the T° sensors positioning in the unit 3.1.3 Label placed in the box 3 cover (i/o REC print board) 3.2 Power supply to the fans and the control devices All the internal cables (fans, controls, sensors, …) to the main switch are factory pre-wired. All the power supply wiring that remains is the main power supply to the main switch(es). Wiring specifications: Unit type 800 1200 2000 3000 4000 Supply Voltage (1) 1 x 230V 1 x 230V 1 x 230V 1 x 230V 3 x 400V + N mum amps 4,1 A 5,2 A 10,6 A 13,2 A 10,6 A (3) Protection type (2) D – 10.000A – AC3 D – 10.000A – AC3 D – 10.000A – AC3 D – 10.000A – AC3 D – 10.000A – AC3 Protection caliber 8A 8A 16 A 20 A 16 A (4) (1) Grounding is compulsory (2) D type “slow” reaction curves - shutoff power 10.000A - AC3. (3) Max current per phase. (4) 3x400V + N. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 6 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 3.3 Power supply for the electric antifreeze coil KWin (option) All the internal cables of the KWin coil to the main switch are factory wired. All that needs to be wired is the main power supply to the main switch. Wiring specifications: Unit type 800 1200 2000 3000 4000 Supply voltage (1) 3 x 400V + N 3 x 400V + N 3 x 400V + N 3 x 400V + N 3 x 400V + N KWin heating capacity 3 kW 4,5 kW 6 kW 9 kW 12 kW mum amps 4,3 A 6,5 A 8,7 A 13,0 A 17,3 A (1) Grounding is compulsory 3.4 Power supply and connections for the electrical post heating coil KWout (option) 3.4.1 Power supply All the internal cables of the KWout coil to the main switch are factory wired. All that needs to be wired is the main power supply to the main switch. Wiring specifications: Unit type 800 1200 2000 3000 4000 Supply voltage (1) 3 x 400V + N 3 x 400V + N 3 x 400V + N 3 x 400V + N 3 x 400V + N KWoutn heating capacity 3 kW 4,5 kW 6 kW 9 kW 12 kW mum amps 4,3 A 6,5 A 8,7 A 13,0 A 17,3 A (1) Grounding is compulsory 3.4.2 Coil Control • A supplied temperature sensor and cable (5m) has to be installed in the supply duct and connected to the KWout control. If the unit is installed outside the sensor cable must be protected. Connect the 2 wires to terminals 10 and 12 of the KWout control (see schematic) Supply T° sensor © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 7 Status 03.09.09 We reserve the right to make changes favouring technical progress. • Instruction manual 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG It is possible to show the actual supply T° on the display of the RC. To do it, it is necessary to connect a second temperature sensor (see schematic). If there is no sensor connected there will be no display of the value on the RC. i/o REC circuit T° sensor • It is possible to overrule the heater’s control system using the following connection, allowing shutting down the post heating using an external contact. i/o REC circuit Post-heating ON/OFF Contact closed = post heating OFF Contact open = post heating ON 3.5 Connecting the post heating water coil (option) The post-heating water coil is delivered with a motorized 3-way valve. 3.5.1 Power supply • • The connection of the power supply to the valve motor is carried out in the factory as well as the connection to the control device, The supplied temperature sensor must be mounted in the supply duct, and must be wired as shown: i/o REC circuit T° sensor © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 8 Status 03.09.09 We reserve the right to make changes favouring technical progress. • ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG The control allows to automatically starting the circulator of the hot water circuit. To do so wire in series (electrical) the OR3 relay contact with the water pump command as following : i/o REC circuit Water pump • OFF ON It is possible to overrule the heater’s control system using the following connection, allowing shutting down the post heating using an external contact. i/o REC circuit Post-heating ON/OFF Contact closed = post heating OFF Contact closed = post heating ON 3.5.2 Water connection (to be made by the installer) • Connection schematic: © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 9 Status 03.09.09 Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. • ® WÄRMERÜCKGEWINNUNG These are the specifications for the water coil connection: Unit type 800 1200 2000 3000 4000 Diameter on the coil Diameter on the valve 1/2’’ 1/2’’ 1/2’’ 1/2’’ 1/2’’ 3/4’’ 3/4’’ 3/4’’ 3/4’’ 3/4’’ Coil Capacity (*) 4,5 kW 8,0 kW 13,2 kW 19,4 kW 27,8 kW Water flow (*) 199 l/h 353 l/h 585 l/h 857 l/h 1200 l/h Pressure loss (*) 1,4 kPa 6,5 kPa 20,4 kPa 11,1 kPa 26,8 kPa (*) Nominal values for following selection conditions: air in T°: 18°C, water in/out T: 90/70°C. For other conditions refer to the lobal selection software or provided data sheet for the project. 3.6 Starting the TAC3 control The TAC3 control is delivered assembled and factory wired. Only the RC (Remote Control) must be installed where chosen and wired by a qualified installer. The TAC3 control consists of 3 parts (see 3.1): • A CBr4 TAC3 REC circuit which is factory assembled wired and tested in the unit. No connections are to be made by the installer to this part. • An i/o REC circuit which is factory assembled wired and tested. It is located on the outside of the front panel of the unit. All the installer’s wirings and settings are made on this component. • A remote control RC TAC3 REC which must be properly wired by the installer to the i/o REC circuit. This component allows full configuration of the unit, display of all the parameters as well as the control of the fans. 3.6.1 General schematic of the control device Located outside the unit 3.6.2 Connecting the remote control to the i/o REC module The connection between the various modules is made by a communication bus. Once you know where to install the RC follow these steps to connect the RC to the i/o module: © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 10 Status 03.09.09 Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG 3.6.2.1 Open the RC casing Using a small screwdriver unlock the 4 pins Remove the cover 2 pins on each side Points for fixation of the casing (spacing = 88mm) RC dimensions = 122 x 66mm RC wiring terminals Caution: • The RC is the module that saves the setup data. If you need to replace the RC you need to re-configure the setup. It is therefore important to fill in the setup datasheet after 1rst installation (see appendix) to remember the setup parameters. • For the same reason, it is not possible to operate the without RC. • The RC box is class IP20 and cannot be installed outdoors as such. If you wish to install it outdoors (for instance on the unit) you need to fasten inside a proper watertight box. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 11 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 3.6.2.2 Wiring diagram to connect the RC module to the i/o REC module Cable specifications • Recommended cable: category 5 shielded twisted pair (FTP) cable with a section of 0,26 … 0,50 mm². Use 1 pair to connect GND and +12V and 1 pair to connect B- and A+. • mum cable length: 1000 m. • Keep this communication cable at distance from power cables. • If the unit is installed in a location with high electro-mechanical interference levels: the shielding must be connected on one side to the shielding of the cable connecting the CBr to the i/o REC. • If the unit is installed outside, select a suitable cable for outdoor application (UV light, …). 3.6.3 Selecting the Master « Selecting the master » means the determination of which module of the i/o and the RC will “control” the fans, “controlling” the fans means: • If CA mode is chosen (see 4.1.1), to be the master means to control the start/stop of the fans as well as to select the airflow • If LS or CPs mode (see 4.1.2 and 4.1.3), to be the master means to control the start/stop of the fans as well as to activate/deactivate a different assignment (assignment multiplier). RC is master i/o module is master i/o REC circuit i/o REC circuit Control Visualization Control Visualization i/o module is « master »: contact between terminals IN3 and +12Vdc of i/o module is closed. • The i/o module allows control of the fans through its inputs. • The RC allows to configure and to de visualize all the parameters on the display and with the LEDs, RC module is « master » contact between terminals IN3 and +12Vdc of i/o module is open. • The i/o module is reduced to being an only passive link between the RC and the fans. • The RC allows to configure and to visualize all the parameters on the display and with the LEDs • The RC controls the fans with the OFF / I / II / III keys © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 12 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Wiring diagram Contact closed = i/o module is master, Contact open = RC module master Caution: Use gold plated contact only. The use of this contact enables to switch automatically from RC master to i/o master. Using this you can for instance : • Work in RC master and switch in position i/o master to stop automatically the fans (attention, in this case the inputs K1/K2/K3 on the i/o have to be disconnected from the +12V). • Work in RC master and switch in position i/o master to activate automatically a sleep value (attention K1/K2/K3 on the i/o have to be properly connected to activate this value). © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 13 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG IV. SYSTEM CONFIGURATION INSTRUCTIONS 4.1 Working modes The various working modes give the user the choice on how the airflow must be modulated according to your application. In all the working modes the supply fan will operate according to the assigned mode and parameters. The airflow of the exhaust fan will then equal to a percentage of the actual airflow of the supply fan (noted %EXT / PUL for ratio between exhaust and supply airflows). The control allows configuration of one of the following 4 modes, briefly described hereunder. For more information consult the TAC technology section on our website. • CA MODE: 3 constant airflow assignments for the supply fan are determined by the user (m³h K1, m³h K2 et m³h K3). • LS MODE: The assigned supply airflow is a function of a 0-10V linear signal. The user defines the link with 4 parameters: Vmin, Vmax, m³h≡Vmin et m³h≡Vmax, applied to the following diagram: With m³h≡Vmin < or > m³h≡Vmax (positive or negative link) Using the advanced setup, it is possible to stop the fans once the input signal value has reached a certain upper and/or lower limit. • CPs MODE: This mode can either be applied on the supply or the exhaust. CPs on supply: the airflow of the supply fan(s) is modulated so as to maintain constant a certain pressure value measured by a pressure sensor properly located in the ducting. CPs on exhaust: the airflow of the exhaust fan(s) is modulated so as to maintain constant a certain pressure value measured by a pressure sensor properly located in the ducting. • MODE OFF: Is not a real working mode, it is a way to temporarily shortcut the i/o master setup. It allows, if working in i/o master, to stop the fans with the RC. But then to restart the fans it is required to choose one of the other 3 working modes. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 14 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 4.1.1 CA Mode: setup, operating instructions and wiring diagrams 4.1.1.1 Setup CA mode The setup is made by means of the LCD screen and the 4 knobs SETUP, ↑, ↓ and ENTER of the RC. To start the setup: - Enter in the setup mode using the left knob on the diagram so that the SETUP LED ignites - Press then the SETUP knob until the text ‘SETUP’ appears on the screen. The idea is to select your choice with the ↑↓ knobs and then to confirm your choice by pressing ‘ENTER’. The numbers are introduced digit by digit. 1 2 LANGUAGE Choose your language (English, French, Dutch, German) SUPPLY? If a post heating water coil (option) is mounted in the unit, introduce the assignment T° for the supply airflow. See details in §4.6. xx°C (NV) 3 WORKING MODE 4 m³h K1? Type in supply airflow 1 (will be activated if contact between K1 and +12V of i/o module closed or if position I on RC is selected) 5 m³h K2? Type in supply airflow 2 (will be activated if contact between K2 and +12V of i/o module closed or if position II on RC is selected) 6 m³h K3? Type in supply airflow 3 (will be activated if contact between K3 and +12V of i/o module closed or if position III on RC is selected) 7 %EXH/SUP Type in ratio between exhaust (EXT) and supply (PUL) airflow to create over, under or even pressure. 8 PRESSURE ALARM? The pressure alarm is optional. If you do not wish it select N and skip to step 14. Otherwise select Y. For more details see §4.12. 9 ∆P SUP Type in the pressure increment for the supply airflow. 10 ∆P EXH Type in the pressure increment for the exhaust airflow. 11 INIT Pa REF? Do you wish to (re-)configure the reference pressure for the supply and the exhaust airflows? Y or N. (this is optional if it has been done previously) 12 m³h INIT If Y is selected, enter nominal airflow at which you wish to initialize the reference pressure. (same airflow for exhaust and supply air) 13 Pa REF INIT xxxx m³h Select CA from CA, LS, CPs Initializing the reference pressure… After +/-1 minute, the system will memorize the calculated pressure value of the fan as the reference pressure. While initializing the airflow and pressure on F1 is displayed. xxxx Pa 14 15 ALARM Possibility to reset the alarms. Y or N? RESET? END SETUP End © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 15 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG 4.1.1.2 Operating CA mode with RC module master • One of the 3 assignment constant airflows (m³h K1, m³h K2 et m³h K3) is selected using the I / II / III knobs of the RC. The selection made is highlighted by the corresponding LED on the RC. The exhaust airflow is equal to (%EXT/PUL) of the supply airflow. • The OFF touch allows stopping the fans. • It is also possible to start/stop the fans with an external contact connected to the i/o module: Caution: in this case terminals K1/K2/K3 of the i/o module CANNOT be connected. Closed = fans OFF Open = fans ON Start / stop 4.1.1.3 Operating CA mode with i/o module master One of the 3 assignment constant airflows (m³h K1, m³h K2 et m³h K3) is selected using the K1/K2/K3 terminals on the i/o module. The selection made is highlighted by the corresponding LED on the RC. The exhaust airflow is equal to (%EXT/PUL) of the supply airflow. Wiring diagrams for CA i/o module master i/o REC circuit a) Wiring 1 module to 3 external contacts i/o REC circuit 3 K1 closed Ö airflow m h K1 3 K2 closed Ö airflow m h K2 3 K3 closed Ö airflow m h K3 K1/K2/K3 open Ö softstop Caution K1/K2/K3: Use gold plated contacts only. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 16 Status 03.09.09 Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG b) Wiring 1 module to an COM4 (PLC 4 positions switch) COM4 c) Wiring several i/o modules to 3 external contacts 3 K1 closed Ö airflow m h K1 3 K2 closed Ö airflow m h K2 3 K3 closed Ö airflow m h K3 K1/K2/K3 open Ö softstop Caution K1/K2/K3: Use gold plated contacts only. d) Wiring several i/o modules to 1 COM4 COM4 © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 17 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 4.1.2 LS Mode : setup, operating instructions and wiring diagrams 4.1.2.1 Setup LS mode The setup is made by means of the LCD screen and the 4 knobs SETUP, ↑, ↓ and ENTER of the RC. To start the setup: - Enter in the setup mode using the left knob on the diagram so that the SETUP LED ignites - Press then the SETUP knob until the text ‘SETUP’ appears on the screen. The idea is to select your choice with the ↑ ↓ knobs and then to confirm your choice by pressing ‘ENTER’. The numbers are introduced digit by digit. 1 2 LANGUAGE Choose your language (English, French, Dutch, German) SUPPLY? If a post heating water coil (option) is mounted in the unit, introduce the assignment T° for the supply airflow. See details in §4.6. 00°C (NV) 3 WORKING MODE Select LS from CA, LS, CPs 4 V min? Select minimum voltage value 5 V max? Select mum voltage value 6 m³/h≡Vmin Select constant airflow value for minimum voltage Vmin 7 m³/h≡Vmax Select constant airflow value for mum voltage Vmax 8 % on K3? Select constant airflow multiplier when contact between terminals +12V and K3 is closed, or if position III is activated on the RC. 9 %EXH/SUP Type in ratio between exhaust (EXT) and supply (PUL) airflow to create over, under or even pressure. 10 PRESSURE ALARM? The pressure alarm is optional. If you do not wish it select N and skip to step 16. Otherwise select Y. For more details see §4.12. 11 ∆P SUP Type in the pressure increment for the supply airflow. 12 ∆P EXH Type in the pressure increment for the exhaust airflow. 13 INIT Pa REF? Do you wish to (re-)configure the reference pressure for the supply and the exhaust airflows ? Y or N. (this is optional if it has been done previously) 14 m³h INIT If Y is selected, enter nominal airflow at which you wish to initialize the reference pressure. (same airflow for exhaust and supply air) Pa REF Initializing the reference pressure… INIT After +/-1 minute, the system will memorize the calculated pressure value of the fan as the reference pressure. While initializing the airflow and pressure on F1 is displayed. 15 xxxx m³h xxxx Pa 16 17 ALARM Possibility to reset of the alarms. Y or N ? RESET? END SETUP End © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 18 Status 03.09.09 We reserve the right to make changes favouring technical progress. Instruction manual 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG 4.1.2.2 Operating LS mode with RC module master • Starting/stopping the fan is carried out with knobs I/III and OFF. • The assignment value for the supply constant airflow is a function of a 0-10V signal connected to terminals K2 and GND of the i/o module. The link between voltage and airflow is linear. The exhaust constant airflow is equal to %EXT/PUL of the supply airflow. (except if 2 separate 0-10V signals are used to determine exhaust and supply constant airflows, see advanced setup). • By pressing knob III of the RC you activate the pre-set multiplier (% on K3). • It is possible to start/stop the fans with an external contact connected to the i/o module (see diagram hereunder). Caution: terminals K1/K2/K3 of the i/o module CANNOT be connected. i/o REC circuit Start / stop Closed = fans OFF Open = fans ON Caution: use gold plated contacts only a) Wiring diagram with 1 i/o module connected to 1 sensor i/o REC circuit (*) b) Wiring diagram with several i/o modules connected in parallel to 1 sensor + - 0-10 Vdc (*) (*) K2Ö 0-10V signal, mum impedance allowed: 1500 Ω © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 19 Status 03.09.09 We reserve the right to make changes favouring technical progress. Instruction manual 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG 4.1.2.3 Operating LS mode with i/o module master The assignment value for the supply constant airflow is a function of a 0-10V signal connected to terminals K2 and GND of the i/o module. The link between voltage and airflow is linear. The exhaust constant airflow is equal to %EXT/PUL of the supply airflow. (except if 2 separate 0-10V signals are used to determine exhaust and supply constant airflows, see advanced setup). Starting/stopping the fans is carried out with entry K1 on the i/o module. The K3 entry of the i/o module can be used to activate the pre-set multiplier (% on K3). Wiring diagrams To locate i/o module see section 3.1 a) Wiring diagram with 1 i/o module (*) b) Wiring diagram with several i/o modules in parallel + 0-10 Vdc (*) - (*) K1 closed Ö soft start K1 open Ö softstop K2 Ö 0-10V signal, mum impedance allowed: 1500 Ω K1+K3 closed Ö % on K3 activated K3 open Ö % on K3 inactive Caution: use gold plated contacts only © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 20 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 4.1.3 CPs Mode : setup, operating instructions and wiring diagrams 4.1.3.1 Setup CPs mode The setup is made by means of the LCD screen and the 4 knobs SETUP, ↑, ↓ and ENTER of the RC. To start the setup: - Enter in the setup mode using the left knob on the diagram so that the SETUP LED ignites - Press then the SETUP knob until the text ‘SETUP’ appears on the screen. The idea is to select your choice with the ↑ ↓ knobs and then to confirm your choice by pressing ‘ENTER’. The numbers are introduced digit by digit. 1 2 3 4 LANGUAGE Choose your language (English, French, Dutch, German) SUPPLY? If a post heating water coil (option) is mounted in the unit, introduce the assignment T° for the supply airflow. See details in §4.6. xx°C (NV) WORKING MODE CPs on SUPPLY 5 % on K3? 6 %EXH/SUP Select CPs from CA, LS, CPs Select if you wish the constant pressure to operate on the exhaust or on the supply airflow. Input of multiplier on the CPs assignment when contact between terminals +12V and K3 in the i/o module is closed or if knob III is activated on the RC Type in ratio between exhaust (EXH) and supply (SUP) airflow to create over, under or even pressure. New initialization of the CPs constant pressure assignment ? Y or N INIT CPs REF? INIT via If Y is selected in 7 then select if you want to initialize the CPs reference automatically 8 AIRFLOW? via the airflow or manually via the pressure value. If INIT CPs via AIRFLOW (default): the unit automatically determines the reference pressure 9 m³h INIT Enter nominal airflow to determine assignment pressure CPs. Initializing of CPs busy. CPs INIT After 1 minute the system will memorize the pressure measured by the sensor xx,x V 10 corresponding to the nominal airflow. Display of the actual airflow of the supply or exhaust fan (F1 or F3) and of the actual xxxx m³h sensor value. xxxx Pa ALARM Possibility to reset the alarms Y or N 11 RESET? END The configuration of the system is finished. 12 SETUP If INIT CPs via PRESSURE (see advanced setup): the user determines the reference pressure CPs REF? Enter the assignment pressure value. 9 xx,x V ALARM Possibility to reset the alarms Y or N 10 RESET? END The configuration of the system is finished 11 SETUP 7 Note that the CPs mode can be either active on the supply or the exhaust side of the unit (see 4, in table above): CPs on SUPPLY air : The airflow delivered by the supply fans is automatically modulated to obtain a constant pressure as measured by the pressure sensor in the duct. The exhaust airflow is equals to %EXT/PUL of the supply airflow. CPs on EXHAUST air : The airflow delivered by the exhaust fans is automatically modulated to obtain a constant pressure as measured by the pressure sensor in the duct. The supply airflow is equals to 1/(%EXT/PUL) of the exhaust airflow. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 21 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 4.1.3.2 Operating CPs mode with RC master • The start/stop of the fans is controlled by knob I and OFF. • The pressure sensor is connected between K2 and GND of the i/o module • The ‘III’ knob on the RC allows activating the airflow ‘multiplier % on K3’ on the airflow assignment. • It is possible to start/stop the fans with an external contact connected to i/o module. In this case, terminals K1/K3 of the i/o module must not be connected ! i/o REC circuit Start / stop Closed = fans OFF Open = fans ON Caution: use gold plated a) Wiring of 1 i/o module to 1 sensor i/o REC circuit (*) b) Wiring in parallel of several i/o modules to 1 sensor + - 0-10 Vdc (*) (*) K2 Ö 0-10V signal, mum impedance allowed: 1500 Ω 4.1.3.3 Operating CPs with i/o module master • The start/stop of the fans is controlled by entry K1 of the i/o module. • The pressure sensor is connected between K2 and GND of the i/o module • K3 on the i/o module can be used to activate the multiplier ‘% on K3’ on the airflow assignment © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 22 Status 03.09.09 We reserve the right to make changes favouring technical progress. Instruction manual 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG a) Wiring 1 i/o module to 1 sensor (*) b) Wiring several i/o modules in parallel to 1 sensor + 0-10 Vdc (*) K1 closed Ö soft start K1 open Ö softstop K2 Ö 0-10V signal, mum impedance allowed: 1500 Ω K1+K3 closed Ö % on K3 activated K3 open Ö % on K3 inactive Caution: use gold plated contacts only 4.2 Bypass control with ’s TAC3 control According to inside and outside temperatures, the control TAC3 will monitor the opening/closing of the 100% bypass damper. The by-pass is delivered completely wired and motorized from factory. No wiring or installation is required by the installer. The O.R.4 relay (SAT3 option) of the i/o REC print board indicates the opening / closing of the bypass. Operating description : • Opening of 100% by-pass if all following conditions are met: - Outside T° (sensor T1) < inside T° (sensor T2) – 1°C. - Outside T° (sensor T1) > 15°C - Inside T° (sensor T2) > 22°C. • Closing of 100% by-pass if one of the following conditions is met: - Outside T° (sensor T1) > inside T° (sensor T2). - Outside T° (sensor T1) < 14°C - Inside T° (sensor T2) < 20°C. All these temperature SET values can be modified using ADVANCED SETUP. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 23 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG 4.3 Standard built in antifreeze protection of the heat exchanger This functionality is built in the standard control and must not be configured by the installer. It is automatically de-activated if an optional KWin pre-heater (see §4.4) is installed in the unit. Description: In order to avoid the risk of frosting the heat exchanger, the supply airflow is linked to the temperature value of the exhaust airflow measured after the heat exchanger (sensor T3). The exhaust airflow remains unchanged. • T°(S3) > +5°C: the assigned airflow is as defined by SETUP • +1°C < T°(T3) < +5°C : the airflow assigned by SETUP is automatically modified as follows : - If CA or LS working mode : the supply airflow will progressively drop down to 33% (AFlow) of the assigned airflow (AFn) - If CPs mode, the assigned pressure will drop to 50% (AFlow) of the assigned pressure (AFn) - In these conditions LED AF is ON. • T°(T3) < +1°C : the supply airflow is stopped for as long as T°(T3) < +1°C. In these conditions LED AF is blinking. All these temperature SET values can be modified using ADVANCED SETUP. Antifreeze diagram : S3 (°C) 5°C LED AF ON 1°C LED AF indicating AF low AF n 4.4 Antifreeze the heat exchanger with pre-heating KWin (option) The series features a fully automated pre-heating coil. Its capacity is modulated according to the actual heating requirements to avoid frosting the heat exchanger. The control automatically regulates the coil’s capacity to maintain constant an assigned exhaust airflow temperature after the heat exchanger (value same as S3). The Kwin option is made of 3 parts: • A regulator provided with a display: see picture below • A solid state relay (SSR) to modulate the heating capacity of the coil • A T° sensor The 3 elements are delivered fully wired and mounted (plug and play) © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 24 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG 4.4.1 Setup of the KWin pre-heating coil control The Kwin is full pre-configured: PID parameters as well as the assignment. If you need to modify the assignment: see 4.4.2 4.4.2 Modifying the assigned floor T° The assignment is pre-set in factory. It’s then usually not necessary to modify it. Caution: if you modify the KWin assignment you have also to change the parameter T° AF in the advanced setup of the TAC3 . • Make sure the unit is properly connected and is power supplied. • Start the fans at nominal airflow (if CA or LS) or pressure (if CPs). • On the display, set the ‘floor T°’ not to be to be exceeded in the exhaust airflow after the heat exchanger. (the default value is +1°C): -Press ‘P’ on the KWin regulator until SP1 appears on the display -Modify floor T° value using knobs ↑ and ↓ -Press ‘P’ to validate your choice. Display of actual T° measurement Press to increase assignment T° (press ‘P’ first) Press to decrease assignment T° (press ‘P’ first) Press ‘P’ to enter in the assignment configuration mode Indicates if actual T° is lower (◄), equals (■) or higher (►) than assignment T° LED indicating that regulator is ON and the coils are cycling to pre-heat the supply air. This means: - the actual T° is < assigned ‘floor T°’ - AND thermal protections are not activated, - AND the fans are running, - AND the by-pass is closed 4.4.3 Control features of the TAC3 • The TAC3 control only allows the heating coil to be operated if the supply fans are in working. • The post-ventilation feature (see advanced setup) is automatically activated: If the fans are requested to stop, the R3 relay is opened, and therefore the power supply to the coils is also shut down. The fans continue running for 90 seconds to insure post-ventilation of the electrical coils. • If conditions make that the pre-heating coil KWin does not deliver enough capacity to reach the ‘floor T°’ assignment, and therefore not insuring the anti-frost duty, the control will modulate the in and out airflows as follows: © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 25 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG 4.4.3.1 If T° < -1°C and T° < (floor T° - 1,5°C), for more than 5 minutes: If CA and LS mode: reduction of in and outgoing airflows to 66% of the assigned airflows. If CPs Mode: reduction to 75% of the assigned pressure. This setup is maintained during 15 minutes, after which the 100% airflow/pressure assignment is reestablished. Actions on RC LED Display text ALARM AF T° ALARM REDUCED AIRFLOW RED LED Pa LED ALARM / ON Actions on i/o REC circuit Relay AL1 Relay R2 on SAT3 (O.R.1) / / Action on fans LED AF ON Assignment reduction 4.4.3.2 If T° < -5°C during 5 minutes the unit is stopped: Actions on RC LED Display text ALARM AF T° ALARM STOP FANS RED LED Pa LED ALARM / ON Actions on i/o REC circuit Relay AL1 Relay R2 on SAT3 (O.R.1) Alarm / status Action on fans LED AF Blink Stopped Restart is made by resetting (see 4.12) 4.5 KWout post heating electrical coil control (option) The series features a fully automated post-heating electric coil (option). Its capacity is modulated according to the actual heating requirements to obtain a constant supply air temperature . The control automatically regulates the coil’s capacity to maintain constant an assigned supply airflow temperature. The KWout is made of 4 parts: • A regulator provided with a display: see picture below • A solid state relay (SSR) to modulate the heating capacity of the coil • A sinker to dissipate the heat produced by the SSR • A T° sensor The 4 elements are delivered fully wired and mounted (plug and play) © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 26 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG 4.5.1 Setup of the KWout post-heating coil control • Make sure the unit is properly connected and is power supplied. • Start the fans at nominal airflow (if CA or LS) or pressure (if CPs). • On the KWout regulator , set the ‘assigned air T°’, the temperature to be kept constant after the heating coil (caution: mum 50°C) - Press ‘P’ on the regulator until SP1 appears on the display - Enter assignment T° value using knobs ↑ and ↓ - Press ‘P’ to validate your choice. • Initializing the PID parameters: this is pre-set in factory. You should then not to have to change this. If you need to modify the PID parameters (for example if your T° is not stable due to inappropriate PID parameters) This operation must be carried out in order to obtain a good dynamic behavior of the coil control: - Press ‘U’ until ‘Tune’ appears on the screen -The automatic initialization of the PID parameters starts. The red led is lit. DO NOT modify the airflow instructions during this phase (+/- 90 seconds). - When optimization of the PID parameters is done, the red led is off and the control directly starts to modulate the coils capacity to reach the previously assigned air temperature. - Once this initialization done, it is possible to modify the assignment T°. LED blinks during initialization of PID parameters Actual T° Press U to Start PID parameters initialization Increase assignment T° value (press P before) Decrease assignment T° value (press P before) Press P to enter assignment T° configuration Indicates if actual T° is lower (◄), equals (■) or higher (►) than assignment T° LED indicating that regulator is ON and the coils are cycling to pre-heat the supply air. This means: - the actual T° is < assigned ‘floor T°’ - AND thermal protections are not activated, - AND the fans are running, - AND the by-pass is closed 4.5.2 Modification of the assigned floor T° (caution: mum 50°C) To set the assignment T° to be maintained constant by the KWwout control: - Press ‘P’ on the KWout regulator until SP1 appears on the display - Modify assignment T° value using knobs ↑ and ↓. - Press ‘P’ to validate your choice, and return to the actual T° display by pressing ‘P’ again © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 27 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 4.5.3 Control features of the TAC3 • The TAC3 control only allows the heating coil to be operated if the supply fans are working. • The post-ventilation feature (see advanced setup) is automatically activated: If the fans are requested to stop, the R3 relay is opened, and therefore the power supply to the coils is also shut down. The fans continue running for 90 seconds to insure post-ventilation of the electrical coils. • It is possible to display the Supply air T° on the screen of the RC if a T° sensor T5 is connected to the i/o module (see 3.4.2.) • It is possible to stop the post-heating with an external contact connected to IN6. (see 3.4.2.) 4.6 NV post heating of the supply air with a water coil (option) A NV post-heating water coil can be installed in the to maintain a pre-set air T°. The actual capacity delivered is completely monitored by the control with the motorized 3-way valve (supplied, but to be installed by the installer). Control features of the TAC3 : • Monitoring the 3-way valve to keep assignment T° constant using supplied sensor T° value. • Engaging a relay to start a water circulator (output O.R.3 on i/o module - see 3.5.1.) • Antifrost protection of the water coil based on the value of T4 (T° sensor provided and pre-wired). If value T4 <1°C then the 3 way valve is opened and contact for circulator is closed (see 3.5.1.) during 15 minutes • Possibility to stop the post-heating with an external contact connected to terminal (IN6) on the i/o module (see 3.5.1.). • Assignment failure: see 4.12. • Sensor failure alarm : see 4.12. 4.7. Working with CT option If a damper (CT) is mounted on the the starting of the fans is temporized by 30 seconds to assure the opening of the damper before to start the fans. 4.8 Display on the RC a) Standard display By default, only airflow and fan pressure values as well as alarm status are displayed on the LCD. b) Display all the parameters Press on the left knob on the diagram so that the SETUP LED ignites By pressing ↑ and ↓ it is possible to display the status of all the working parameters: - type and built in options (CT, pre/post heating) - working mode and set values - airflow/pressure of each fan - pressure alarm setup (CA/LS working mode only) - alarm status - status of K1/K2/K3 inputs on the i/o module - status of IN1/IN2/IN3/IN4/IN5/IN6/IN7/IN8 inputs on the i/o module - status of the bypass - status of the anti-freeze protection - T° values of sensors 1/2/3/4/5 (4 and 5 = options) - status of the CT (option) © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 28 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG 4.9 Fan failure alarm It is possible with a SAT3 mounted on the i/o module (option) to provide the fan status (control if actual delivered airflow > 20% of airflow assignment) or if they are stopped, using the R3 relay of one of the 2 SAT3 (O.R.2). This feature provides an increased safety with regard to the start instruction control, because there is a control on the fact that the fan is actually running (closed loop principle) Wiring diagram: 4.10 Actual airflow / pressure output signals A 0-10V signal representing the actual airflow or the actual pressure delivered by one of the selected fans with a linear relation is a standard feature. The output signals are located between terminals OUT3/OUT4 and GND on the i/o module. Default setup : OUT3 = airflow fan 1 (supply fan) and OUT4 = pressure fan 1 (supply fan). Table link between 0-10V signal and actual pressure or airflow value. (Linear equation) 801 Pressure (Pa) 0V 10 V Airflow (m3/h) 0V 10 V 1201 2001 3001 4001 0 675 0 780 0 1090 0 1060 0 1090 0 960 0 1450 0 2400 0 3600 0 2400 (*) (*) airflow per fan. You can also take the total airflow: 10V = 4800 m³/h Via the ‘advanced setup’ it is possible to connect any of these 2 OUT signals to the airflow or pressure value of any fans. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 29 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Wiring diagram of output signals: default: OUT3 = actual airflow of fan 1 (supply) default: OUT4 = actual pressure of fan 1 (supply) 4.11 Advanced setup Warning: using this feature requires a good knowledge of the control system. The advanced configuration allows modifying the parameters not present in the basic configuration: - Stop fans is pressure alarm activated - Fans start torque - Fire alarm configuration - Bypass T° - Airflow if bypass open - AF (anti-freeze) configuration - NV speed (option if NV installed) - In mode LS: stop of the fans if Vin < and/or > set value(s) - In mode CPs: - positive or negative logical - reaction speed of the CPs algorithm - OUT3/OUT4 definition - Post-ventilation configuration - Fan run time configuration - Display alarms only - Access code configuration - Factory reset © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 30 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 4.12 Alarms 4.12.1 Alarm types Type 1: Alarm indicating a fan failure (1). This alarm indicates a failure of fan Fx. This problem is usually caused by the motor. If not the failure can be caused by an internal cable or a control. See 1 in table below. Type 2: Alarm on the pressure variation (CA and LS modes only). This alarm indicates a pre-established pressure level has been reached on fan Fx. See 2 in table below. Type 3: Alarm indicating a problem while initializing reference pressure for a pressure alarm (1). 3 possibilities (See 3 in table below) : - Actual airflow < requested airflow : The requested working point is ‘too high’ (too much pressure) for the mal available pressure at the requested airflow for this fan. - Actual airflow > requested airflow: the nominal airflow requested to initialize the pressure alarm cannot be reached because the lower limit of the fan’s operating zone has been reached. - Very unstable pressure (pumping). See 3 in table below. Paréf cannot be identified and the fans are stopped. Press ‘RESET’ using ‘SETUP’ on the RC, or with the ‘RESET’ key on the i/o module. - If it occurs during initializing an alarm pressure 2 options: 1. No action is taken: the control will operate without pressure alarm 2. Corrective action is taken (change the working point to one well located in the working zone of the fan, by reducing the pressure system, modifying the nominal airflow, …) and restart the setup operation…. - If it occurs during initializing of the assignment pressure in CP mode : A corrective action must be taken (change the working point to one well located in the working zone of the fan, by reducing the pressure system, modifying the nominal airflow, …) and restart the setup operation…. Type 4: Alarm indicating the system cannot fulfill the assignment (1). The assignment (keeping a certain airflow or a certain pressure constant) cannot be fulfilled because the upper or lower limit of the fan’s working zone has been reached. See 4 in table below. Type 5: Alarm indicating a data failure in the control circuit Crucial data from the circuit board has been lost. Try a TOTAL RESET of the data using the advanced setup (see website). If still not solved send the defect RC for reprogramming. See 5 in table below. Type 6: Fire Alarm with an external contact connected to a fire detection system See 6 in table below and paragraph 4.13. Type 7: Alarm indicating maintenance is expected. (for configuration see “advanced setup) SERVICE ALARM: indicates the fan operating time (in hours) has exceeded a certain limit set during the configuration.. STOP FAN: indicates the fan operating time (in hours) has exceeded a certain limit set during the configuration. This alarm stops the fans. See 7 in table below. Type 8: Alarm indicating a communication breakdown between RC, i/o module and central circuit CBr4. Verify if the wirings are correct. See 8 in table below. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 31 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Type 9: Alarm indicating a T° sensor S1/S2/S3 failure. One or more of the T° sensors S1/S2/S3 connected to the CBr4 module and mounted on heat exchanger is defect or not connected. These sensors are crucial for the by-pass control and the antifrost procedure. After correction of the failure press ‘RESET’ with SETUP of the RC or press ‘RESET’ on the i/o module. See 9 in table below. Type 10: Alarm indicating failure on T° sensor S4 (only with NV option). It indicates that the T° sensor S4 located on the coil and connected to the CBr4 module is defect (open or short circuit) or not connected. This sensor is used to avoid frosting of the NV coil. In this case, as a safety measure, the 3 way valve is opened and the contact used to start the circulator is closed. After fixing the failure, press ‘RESET’ with SETUP of the RC or press RESET on the i/o module. See 10 in table below. Type 11: Alarm indicating failure on T° sensor S5 (only with NV option). It indicates a failure of the T° sensor located in the supply duct and connected to the i/o module (opened or short circuit) or that it is not connected. This sensor is used to regulate the post-heating function. After fixing the failure, press ‘RESET’ with SETUP of the RC or press RESET on the i/o module. If an electric post heater is used, S5 is only used to display the T° and has no control function. No alarm is generated in case of failure in this case. See 11 in table below. Type 12: Alarm indicating that the assigned T° cannot be reached (only with NV option). If the actual T° is lower than the assigned T° for more than 15 minutes with the valve fully opened until. See 12 in table below. Type 13 and 14: Alarm indicating antifreeze alert (only with KWin option). In certain air T° conditions as measured on the exhaust airflow after the heat recovery, indicating that the Kwin has reached its limit, the control can take over to guarantee the antifrost function: • Alarm type 13: If T° < assignment T°-1,5°C for more than 5 minutes: supply and exhaust airflow reduction of 33% if CA or LS and of 25% if CPs, for 15 minutes. • Alarm type 14: If T° < -5°C during 5 minutes, fans are stopped. Press ‘RESET’ with SETUP of the RC or press RESET on the i/o module to restart the unit. See 13 and 14 in table below. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 32 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG 4.12.2 Alarm table Actions on RC Type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 Display (1) Action on fans Actions on i/o module LED ALARM LED Pa LED ALARM AL1 relay R2 relay Of SAT3 (O.R.1) / LED AF ALARM FANx PRESSURE ALARM ALARM INIT Pa ALARM CA, LS or CPs DATA ERROR FIRE ALARM ALARM SERVICE Red / ON / Red ON Alarm status / / Stopped Fermé / / (2) Red / ON Alarm status / / / Stopped / / ON / / / Red / ON Alarm status Alarm status Alarm status / / Stopped Red / ON / / / / Stopped (3) / Red / ON FAN STOP SERVICE CB COM ERROR ALARM T° SENSOR 1/2/3 ALARM T° SENSOR 4 ALARM T° SENSOR 5 ALARM POSTHEAT T° TOO LOW AF T° ALARM AIRFLOW REDUCED AF T° ALARM STOP FANS Red / ON Alarm status Alarm status Alarm status / / Stopped Red / blink / / Stopped Red / ON / / Stopped Red / ON / / / / / / ON Alarm status Alarm status / Red / ON Red / / / / Red / ON / / ON Reduced airflow Red / ON Alarm status / blinking Stopped / = no action (1) detailed text is displayed in successive screens. (2) Unless the status has been changed in advanced setup to stop the fans. (3) See details in 4.13. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 33 Status 03.09.09 Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. ® WÄRMERÜCKGEWINNUNG 4.12.3 Wiring diagram of relays when alarms O.R.1 O.R.2 4.13 Fire alarm The control can be connected to a fire detection system to : - stop/start the supply/exhaust fans according to fire regulations - set the airflows in case of fire alarms according to fire regulations - allow firemen to overrule the existing setup and start/stop the fans as needed 4.13.1 Configuration The supply / exhaust airflow configuration is made using the advanced setup. 4.13.2 Wiring diagram of fire alarm If IN4 - 12V closed = fire alarm activated If IN4 – 12V closed and, • IN7 - 12V closed = force start the supply fan(s) at pre-programmed airflow. • IN7 - 12V open = force stop the supply fan(s). • IN8 - 12V closed = force start the exhaust fan(s) at pre-programmed airflow. • IN8 – 12V open = force stop the exhaust fan(s). © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 34 Status 03.09.09 Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. ® WÄRMERÜCKGEWINNUNG Appendix 1: ADVANCED SETUP The advanced setup allows to activate certain features or to modify certain parameters: To start the advanced setup, press simultaneously on ‘SETUP’ and ‘ENTER’ until the text ADVANCED SETUP appears on the screen. Principle: make selections via buttons ↑ ↓, then press ‘ENTER’. The numbers are introduced digit by digit. Mode CA LS CPs Step 12 Text on screen ENTER ACCES CODE 0000 Description If the access code procedure has been activated (see step 28) you will need to enter the access code before going any further. STOP FAN IF V<Vlow? N Stop the fans automatically if 0-10V signal value is < Vlow Vlow: xx,x V If Y was selected on step 4, fill in value of Vlow V>Vhigh? N Stop the fans automatically if 0-10V signal value is > Vhigh Vhigh: xx,x V If Y was selected on step 6, fill in value of Vhigh 0-10V ON K3? N Functionality to control supply fans through a 0-10V signal connected on entry K2 and exhaust fans through another 0-10V signal connected on entry K3. (Same link voltage/airflows for both entries) If CPs mode is configured ---CPs 8 CPs SPEED? 10 Tuning of the reaction speed of the CPs algorithm. The default value is 10 and is the highest possible value. Each increment of -1 corresponds to a doubling of the reaction time (10=T, 9=2xT, 8=4xT, …). This feature is very sensible, we recommend it only when operating in constant pressure systems where the system is a room and not a duct. ---CPs LOGIC? NEGATIVE Configuration CPs mode logic: ¦Negative logic: - the airflow decreases when signal on K2 > assignment value - the airflow increases when signal on K2 < assignment value ¦Positive logic: - the airflow increases when signal on K2 > assignment value - the airflow decreases when signal on K2 < assignment value If LS mode is configured --LS 34 --LS --LS - 4.1 56 --LS --LS - 6.1 7 9 If CA or LS mode is configured CA --10 11 PRESSURE ALARM: STOP FAN? N For all working modes (CA, LS CPs) CA LS CPs 12 13 START TORQUE? 2% 14 FIRE AL CONFIG? N Functionality to automatically stop the fans in case of alarm pressure (press RESET to restart fans after correction of problem) Fan starting torque can be modified here. (by default 2%) Possibility to define the supply and exhaust airflows in case of fire alarm. CA LS CPs CA LS CPs 14.1 SUPPLY? xxxx m³h Enter the supply airflow in case of fire alarm. CA LS CPs 14.2 EXHAUST? xxxx m³h Enter the exhaust airflow in case of fire alarm. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 35 Status 03.09.09 Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. ® WÄRMERÜCKGEWINNUNG CA LS CPs 15 16 17 BYPASS T VALUES: T1: 15° T2: 22° Possibility to setup temperature values: outdoor T° (T1) and indoor T° (T2) controlling the opening/closing of the bypass. • Opening of bypass of all following conditions are met : -Outdoor T° (sensor S1) < Indoor T° (sensor S2). -Outdoor T° (sensor S1) > T1. -Indoor T° (sensor S2) > T2. • Closing of bypass if one of the following conditions is met:: -Outdoor T° ((sensor S1) > indoor T° (sensor S2). -Outdoor T° (sensor S1) < T1 1°C. -Indoor T° (sensor S2) < T2 - 2°C. CA LS CPs 18 19 SET m³h IF BYPASS OPEN? N Possibility to define different exhaust and supply airflow when bypass is open.If Y is selected these airflows become independant from the airflow assignment defined by the working mode chosen and the status of entries K1, K2, K3, when the bypass is closed. CA LS CPs 19.1 SUPPLY 0000m³h If you have selected Y at step 19 enter supply airflow to be delivered when bypass is open. CA LS CPs 19.2 EXHAUST 0000m³h If you have selected Y at step 19 enter exhaust airflow to be delivered when bypass is open CA LS CPs AF? N If option KWin (pre-heat) is not installed: Option to activate (Y) or not (N) the anti-freeze system (supply air modulation) for the heat exchanger ? CA LS CPs 20.1 CONFIG AF? N If Y is selected in step 20: Option to edit the anti-freeze system values. CA LS CPs 20.1.1 T° LOW AF: 1°C If Y is selected, go to step 20.1 (you have opted to change the anti-freeze values), enter here the lower value for the anti-freeze system. CA LS CPs 20.1.2 T° HIGH AF: 5°C If Y is selected, go to step 20.1 (you have opted to change the anti-freeze values), enter here the higher value for the anti-freeze system. CA LS CPs 20.1.3 AF STOP FAN? Y CA LS CPs 21 T° AF: +1.0°C If Y is selected, go to step 20.1 (you have opted to change the anti-freeze values), enter here your choice to stop or not the fan when the T° reaches values < T°LOW. If the KWin option is installed: possibility to modify the anti-freeze set point value (exhaust T° after the heat recovery exchanger). CA LS CPs 22 NV SPEED? 05 If the NV option is installed: Tuning of the reaction speed of the post-heating algorithm. The default value is 05 and corresponds to the middle value. Each increment of -1 corresponds to a doubling of the reaction time (05=T, 04=2xT, 03=4xT, …). Each increment of +1 corresponds to a reduction by 2 of the reaction time (05=T, 06=T/2, 07=T/4, …). This feature is very sensible, we recommend it only if the T° is not stable enough due to the reaction speed. CA LS CPs 23 OUT3 m³h F1 CA LS CPs 24 OUT4 Pa F1 Selection of the information present on the 0-10V output OUT3: Select information (airflow or pressure) and fan (F1-F4) to be outputted on OUT3 (default is airflow of fan F1). Selection of the information present on the 0-10V output OUT4: Select information (airflow or pressure) and fan (F1-F4) to be outputted on OUT4 (default is pressure of fan F1). 20 © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 36 Status 03.09.09 Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. CA LS CPs CA LS CPs CA LS CPs CA LS CPs CA 25 ® WÄRMERÜCKGEWINNUNG POST VENT? N Possibility to activate a post-ventilation (continue to run the fan for some time after softstop has been activated). Caution: if preheat KWin = yes and/or postheat type KWout is installed then the POSTVENT est automatically activated and can not be set at NO. TIME PV 0090 sec If you have selected Y on step 25 enter time of duration of post-ventilation in seconds. Attention: if an electrical preheat (KWin) or postheat (KWout) is installed this time is preset to 90sec and may not be reduced. FAN RUN TIME? N Possibility to activate a runtime counter. How much time the fans have been running. This can help to generate a maintenance procedure, or to stop the fans once a certain runtime is reached. 26.1 TIME RESET? N If Y was selected at step 26 you have here the possibility to set the runtime counter at 0. LS CPs 26.2 DISPLAY TIME? N If Y was selected at step 26 you have here the possibility to display the actual runtime. CA LS CPs 26.3 SERVICE ALARM? N If Y was selected at step 26 you have here the possibility to request a runtime alarm service or not. CA LS CPs 26.3.1 TIME? 000000 h If Y was selected at step 26.3 you have here the possibility to set the runtime (in hours) after which a maintenance alarm must be activated. CA LS CPs 26.4 STOP FAN? N If Y was selected at step 26 you have here the possibility to request all fans to stop after a certain runtime. CA LS CPs 26.4.1 TIME? 000000 h If Y was selected at step 26.4 fill in the runtime (in hours) after which you want all fans to be automatically stopped. CA LS CPs 27 DISPLAY ALARM ONLY? N Possibility to only display the alarms on the screen. "Fan OK" will then be displayed when no alarm is activated. CA LS CPs 28 ACCESS CODE? N Possibility to activate an access code to control inside the advanced setup. CA LS CPs CODE 0000 If Y is selected at step 28, enter here the access code to advanced setup. CA LS CPs 29 CA LS CPs 30 25.1 26 28.1 FACTORY RESET? N END SETUP the access Possibility to make a complete reset of all the parameters of the CB. If you chose Y all the factory parameters will be regenerated. End of advanced setup. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 37 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG Appendix 2: TECHNICAL INFORMATION - RC TAC3 - ALARMS The RC TAC3 features 14 alarm types : Type 1: alarm on fan failure Type 2: alarm on pressure rise (modes CA and LS only). Type 3: alarm on the reference pressure initialization Type 4: alarm of non respect of assignment Type 5: alarm on CB data error Type 6: fire alarm (external contact to engage fire alarm procedure on ) Type 7: alarm on maintenance failure. (see advanced setup) Type 8: alarm on communication failure between CBr4 - i/o - RC. Type 9: alarm on temperature sensor S1/S2/S3. Type 10: alarm on temperature sensor S4 (with NV option only). Type 11: alarm on temperature sensor S5 (with NV option only). Type 12: alarm on low supply air T°(with NV option only). Type 13/14: alarm on defrosting mode (with preheating Kwin option only). Type 1: alarm on fan failure Describes a fan function default on fan Fx. Check wiring, connections and 230V supply. Otherwise the cause must be a motor failure. RC actions Text displayed ALARM and LED recommended fixes(1) Red ALARM FANx Pa LED LED ALARM / ON CHECK POWER i/o REC circuit actions AL1 R2 relay AF LED Relay of SAT3 (O.R.1) Alarm status / / Fan action stopped SUPPLY AND CABLES CONNECT THEN PRESS RESET IF NOT SOLVED REPLACE CABLE OR CB OR MOTOR (1) this text is displayed in several consecutive screens Type 2: Pressure alarm (CA and LS modes only) This alarm means : -That the calculated pressure value exceeds the accepted level. This level is determined according to the system curve defined by the nominal airflow and the corresponding pressure + the increment, or -That an external pressure device closed the contact between terminals +12V and IN5 of the i/o circuit . RC actions Text displayed ALARM and LED recommended fixes(1) / PRESSURE ALARM Pa LED Red i/o REC circuit actions LED AL1 R2 relay ALARM Relay of SAT3 (O.R.1) ON / Closed Fan action AF LED / / (2) ON FANx © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 38 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG (1) this text is displayed in several consecutive screens (2) Default action is no action, but this can be changed to ‘stop the fans’ with the ‘advanced setup’ feature. Check the filters and clean or replace if necessary. This alarm can also be caused by anything that could cause an undesired pressure rise: damper closed when it shouldn’t, obstacle in ducting,…or by a faulty initialization. Type 3: Alarm on reference pressure initialization At this stage 3 types of problems can occur : - Actual fan airflow < requested airflow: the requested airflow is located at a pressure level the fan cannot reach. - Actual fan airflow > requested airflow : This alarm signals that the nominal airflow requested cannot be reached because the lower boundary of the fan’s working range is reached. The airflow delivered is therefore superior to the requested airflow - Pressure too unstable. In this case, Paref cannot be defined and motor sets itself in “softstop”. To restart, press RESET on the i/o REC circuit, or with the SETUP of the RC: - If this occurs during an alarm pressure setup, the will then operate normally without a pressure alarm. If you wish a pressure alarm anyway, determine the cause (system pressure or configuration, airflow, working zone of fan,…) and re-start setup again. - If this occurs during a CP mode setup, you need to determine the cause (system pressure or configuration, airflow, working zone of fan,…) and re-start setup again. RC actions Text displayed ALARM and LED recommended fixes (1) Red INIT PA ALARM (2) Pa LED LED ALARM / ON i/o REC circuit actions AL1 R2 relay AF LED Relay of SAT3 (O.R.1) Alarm status / / Fan action Stopped (1) this text is displayed in several consecutive screens (2) Texts displayed in the 3 cases : Displayed text Description INIT PA ALARM Actual fan airflow < requested airflow: the requested airflow is located at a pressure level the fan cannot reach. Change the air system, or the airflow requested, or a use bigger fan. (1) ON FANx AIRFLOW TOO LOW Text is displayed on several successive screens DUE TO TOO HIGH PRESSURE REDUCE PRESSURE OR FLOW THEN RESTART PA INIT VIA THE SETUP. PRESS FIRST ON RESET. INIT PA ALARM ON FANx AIRFLOW TOO HIGH MINIMUM MOTOR LIMIT This alarm signals that the nominal airflow requested cannot be reached because the lower boundary of the fan’s working range is reached. The airflow delivered is therefore superior to the requested airflow. (1) Text is displayed on several successive screens © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 39 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG ACHIEVED SET HIGHER AIRFLOW THEN RESTART PA INIT VIA THE SETUP. PRESS FIRST ON RESET. Pressure too unstable. Change the air system or airflow request. (1) INIT PA ALARM Text is displayed on several successive screens ON FANx PA NOT STABLE. CHANGE WORKING POINT THEN RESTART PA INIT VIA THE SETUP. PRESS FIRST ON RESET. Type 4: Alarm for impossibility to execute the airflow assignment These alarms signal that nominal airflow requested cannot be reached because the limits of the fan’s working area have been reached. RC actions Text displayed ALARM and LED recommended fixes(1) / CA, LS or CP ALARM - Pa LED LED ALARM / ON i/o REC circuit actions AL1 R2 relay AF LED Relay of SAT3 (O.R.1) / / Fan action / / CA/LS alarm ( CA or LS mode): The airflow requested cannot be maintained at constant level: 2 different situations can occur : - The airflow requested cannot be held constant because the counter pressure on fan is too high: Text displayed Description CA or LS ALARM This alarm means the requested airflow cannot be reached. ON FAN x (text is displayed on several successive screens). AIRFLOW TOO LOW. REDUCE PRESSURE ON THAT FAN. Requested airflow cannot be held constant because the counter pressure on the fan is too high. - It is activated if actual airflow < 93% of requested airflow and - Deactivated once airflow reaches value > 97% of requested airflow The text appears on different successive screens. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 40 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG - The airflow requested cannot be held constant because the airflow is too low for the working range of the fan: Text displayed Description CA or LS ALARM This alarm signals that The airflow requested cannot be held constant because the airflow is too low for the working range of the fan. ON FAN x AIRFLOW TOO HIGH MINIMUM MOTOR LIMIT ACHIEVED Activated when airflow is > 112% of requested airflow Deactivated when airflow < 108% of requested airflow . The text appears on different successive screens. - CP Alarm (mode CPs): The requested pressure cannot be held constant in 2 cases: - The minimum airflow of the fan is reached and calculated pressure is still superior to requested pressure: Text displayed Description CP ALARM This alarm states that the minimum airflow of the fan is reached and calculated pressure is still superior to requested pressure. ON FAN x PRESSURE TOO HIGH The text appears on different successive screens. MINIMUM AIRFLOW ACHIEVED Activated when pressure is > 112% of requested airflow Deactivated when pressure < 108% of requested airflow. - The mum airflow of the fan is reached and calculated pressure is still inferior to requested pressure: Text displayed CP ALARM ON FAN x PRESSURE TOO LOW Description This alarm states that the mum airflow of the fan is reached and calculated pressure is still inferior to requested pressure. The text appears on different successive screens. MUM AIRFLOW ACHIEVED Activated when pressure is < 93% of requested airflow Deactivated when pressure >97% of requested airflow. Type 5: Alarm for data error This alarm indicates an error in the data of the control circuit. RC actions i/o REC circuit actions Text displayed ALARM Pa LED LED AL1 R2 relay AF LED LED ALARM Relay of SAT3 (O.R.1) Red / ON Alarm / / DATA status ERROR Fan action Stopped To solve this problem make a « factory reset » using the advanced setup (to activate press keys SETUP and ENTER simultaneously until text “ADVANCED SETUP” appears on the screen. Select “factory reset” and press enter.) If not solved circuit has to sent back for a factory reprogramming. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 41 Status 03.09.09 Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. ® WÄRMERÜCKGEWINNUNG Type 6: fire alarm (external contact to engage fire alarm procedure on ) RC actions Text displayed ALARM LED FIRE ALARM Red Pa LED LED ALARM / ON i/o REC circuit actions AL1 R2 relay AF LED Relay of SAT3 (O.R.1) Alarm / / status Fan action Stopped, or running (depends on setup and status of entries IN7 and IN8 of i/o circuit) Wiring diagram of ‘fire alarm’ on the i/o circuit : Contact IN4 - 12V closed = fire alarm activated. If IN4 – 12V closed : • Contact IN7 - 12V closed = Start the supply fan(s) when fire alarm activated (1). • Contact IN7 - 12V open = Stop the supply fan(s) when fire alarm activated (1). • Contact IN8 - 12V closed= Start the exhaust fan(s) when fire alarm activated (1). • Contact IN8 - 12V open = Stop the exhaust fan(s) when fire alarm activated (1). (1) the requested airflow is configured in the advanced setup Type 7: alarm on maintenance failure. (see advanced setup) SERVICE ALARM: This alarm signals that the operating time of the fan(s) exceeds the time limit configured in the setup. This alarm does not stop the fans. RC actions i/o REC circuit actions Fan action Text ALARM Pa LED LED AL1 R2 relay AF LED displayed LED ALARM Relay of SAT3 (O.R.1) Red / ON Alarm / / / ALARM status SERVICE To reset this alarm you need to enter the advanced setup menu and reset the VENT RUN TIME. FAN STOP SERVICE: This alarm signals that the operating time of the fan(s) exceeds the time limit configured in the setup. This alarm stops the fans. i/o REC circuit actions Fan action AL1 R2 relay AF LED Relay of SAT3 (O.R.1) Red / ON Alarm / / Stopped FAN STOP status SERVICE To reset this alarm you need to enter the advanced setup menu and reset the VENT RUN TIME. Text displayed RC actions ALARM LED Pa LED LED ALARM © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 42 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG Type 8: alarm on communication failure between CBr4 - i/o - RC This alarm signals a communication failure between the different modules of the Maxi control. Text displayed RC actions ALARM LED Red CB COM ERROR Pa LED LED ALARM / Blinks i/o REC circuit actions AL1 R2 relay Relay of SAT3 (O.R.1) Alarm / status Fan action AF LED / Stopped Type 9: Alarm for T° sensor failure S1/S2/S3 This alarm signals a failure of one (or more) of the temperature sensors connected on the CBr4. It is either opened, short circuited or not connected. These sensors are used for the bypass and the antifrost control. After correcting the failure carry out a RESET with the SETUP on the RC, or with the RESET key on the i/oREC circuit. Text displayed RC actions ALARM LED Red ALARM T° SENSOR 1/2/3 (1) Pa LED LED ALARM / ON i/o REC circuit actions AL1 R2 relay Relay of SAT3 (O.R.1) Alarm / status Fan action AF LED / Stopped (1) 2 Ursachen des Sensoralarms sind möglich : Displayed text Description ALARM T° SENSOR 1/2/3 This alarm signals that sensor 1/2/3 is not connected or is faulty. IS OPEN OR IS NOT CONNECT. CHECK CONNECT. Check the wiring of the sensor. Otherwise replace the sensor. The text on the LCD is displayed in successive screens. OR REPLACE SENSOR THEN PRESS ON RESET ALARM T° SENSOR 1/2/3 This alarm signals that sensor 1/2/3 is short-circuited. (SHORT-CIRCUIT) REPLACE SENSOR THEN PRESS Replace the sensor. The text on the LCD is displayed in successive screens. ON RESET Type 10: alarm on temperature sensor S4 (with NV option only) This alarm signals that sensor S4 connected to the CBr4 and on the NV water coil is defect or not connected. This sensor is used for the anti-frosting control system of the NV coil. If this occurs the 3 way valve is opened and the O.R.3 contact is closed (used to start circulator). After fixing the failure, carry out a RESET via SETUP on the RC or via RESET key on i/o REC circuit. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 43 Status 03.09.09 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. Text displayed RC actions ALARM LED Pa LED LED ALARM Red / ON ALARM T° SENSOR 4 ALARM (1) ® Instruction manual i/o REC circuit actions AL1 R2 relay Relay of SAT3 (O.R.1) Alarm / status WÄRMERÜCKGEWINNUNG Fan action AF LED / / (1) 2 kinds of alarms are possible : Displayed text Description ALARM T° SENSOR 4 This alarm signals that sensor 4 is not connected or is faulty. IS OPEN OR IS Check the wiring of the sensor. Otherwise replace the sensor. NOT CONNECT. CHECK CONNECT. The text on the LCD is displayed in successive screens. OR REPLACE SENSOR THEN PRESS ON RESET This alarm signals that sensor 4 is short-circuited. ALARM T° SENSOR 4 (SHORT-CIRCUIT) Replace the sensor. REPLACE SENSOR THEN PRESS The text on the LCD is displayed in successive screens. ON RESET Type 11: alarm on temperature sensor S5 (with NV option only) This alarm signals that sensor S5 connected to i/o REC module and in supply air ducting is defect or not connected. This sensor is used for the air temperature control of the NV coil. After fixing the failure, carry out a RESET via SETUP on the RC or via RESET key on i/o REC circuit. If an electrical coil KWout is used, then if this sensor is defect no alarm will be generated, since this sensor is then used only for information. Text displayed RC actions ALARM LED Pa LED LED ALARM Red / ON ALARM T° SENSOR 5 ALARM (1) i/o REC circuit actions AL1 R2 relay Relay of SAT3 (O.R.1) Alarm / status Fan action AF LED / / (1) 2 kinds of alarms are possible : Displayed text Description ALARM T° SENSOR 5 This alarm signals that sensor 5 is not connected or is faulty. IS OPEN OR IS NOT CONNECT. Check the wiring of the sensor. Otherwise replace the sensor. The text on the LCD is displayed in successive screens. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 44 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG CHECK CONNECT. OR REPLACE SENSOR THEN PRESS ON RESET This alarm signals that sensor 5 is short-circuited. ALARM T° SENSOR 5 (SHORT-CIRCUIT) Replace the sensor. REPLACE SENSOR THEN PRESS The text on the LCD is displayed in successive screens. ON RESET Type 12: alarm on low supply air T° (with NV option only) This alarm signals that the assigned supply air T° cannot be reached. (meaning actual T° < assigned T° for more than 15 minutes while 3 way valve on the NV coil fully opened). Text displayed RC actions ALARM LED Red POSTHEAT ALARM Pa LED LED ALARM / ON i/o REC circuit actions AL1 R2 relay Relay of SAT3 (O.R.1) / / Fan action AF LED / / NV T° TOO LOW Type 13 et 14: alarm on anti-frost mode (with preheating Kwin option only In specific T° conditions (when the pre-heating is insufficient) on the exhaust airflow after heat exchange, the control will override the pre-heating coil Kwin control in order to avoid a risk of frosting the heat exchanger. a) Alarm type 13: If T° < (assignment T°- 1,5°C) for more than 5 minutes, the supply and the exhaust airflow are reduced for 15 minutes (ventilation remains balanced). b) Alarm type 14: If T° < -5°C for more than 5 minutes, the fans are stopped. To restart the fans, after explanation of the failure, carry out a RESET via SETUP on the RC or via RESET key on i/o REC circuit. c) Text displayed AF T° ALARM AIRFLOW REDUCED AF T° ALARM RC actions ALARM LED Pa LED LED ALARM Red / ON Red / ON i/o REC circuit actions AL1 R2 relay Relay of SAT3 (O.R.1) / / Alarm status / Fan action AF LED ON Reduced airflow Blinking Stopped STOP FANS © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 45 Status 03.09.09 We reserve the right to make changes favouring technical progress. Instruction manual 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG APPENDIX – Wiring diagrams Option SAT3 © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 46 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Appendix 3: TECHNICAL DOCUMENTATION VISUALIZATION 1. Default Display The default setting displays actual airflow, pressure, and alarm (if activated) of the fans (loop 1 → 9 → 1 …): Step Text on display Description 1 SUPPLY(1) xxxx m³h SUPPLY(1) xxxx Pa SUPPLY2 xxxx m³h SUPPLY2 xxxx Pa EXHAUST(1) xxxx m³h EXHAUST(1) xxxx Pa EXHAUST2 xxxx m³h EXHAUST2 xxxx Pa Alarm xxx Display actual supply fan1 airflow 2 3 4 5 6 7 8 9 (m3/h) Display actual supply fan 1 pressure (Pa) If 4000: Display actual supply fan2 airflow (m3/h) If 4000: Display actual supply fan2 pressure re (Pa) Display actual exhaust fan1 airflow (m3/h) Display actual exhaust fan 1 pressure If 4000: Display actual exhaust fan2 airflow (m If 4000: Display actual exhaust fan2 pressure Display of alarm type (Pa) 3/h) (Pa) 2. Display all parameters By pressing the ↑ and ↓ keys, it is possible to display the status of all the parameters : Step Text on display Description Alarm type if relevant Display of Idcode of heat recovery unit (6 digits) 7 Alarm xxx REC TYPE xxxxxx KW IN ? YES KW OUT ? YES NV ? YES CT IN ? YES MODE xxx 8 SET VAL. xxxx Display of actual assignment in function of setup and K1/K2/K3 status 9 SET VAL. NV: xx°C If NV present: display of the assigned T° 10 %EXH/SUP xxx % Pa ALARM SUPPLY: m³h: xxxx Pa: xxxx Display of the assigned exhaust 1 2 3 4 5 6 11 12 If option KW IN (electrical preheating coil) is present If option KW OUT(electrical postheating coil) is present If option NV (postheating water coil) is present If option CT (inlet damper) is present Display working mode selected (CA, LS, CPf, CPs) / supply ratio If activated, pressure alarm data on supply side If pressure alarm is activated, display of setup values (m3/h, Pa) at which alarm will be turned on for the supply side (CA and LS modes). © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 47 Status 03.09.09 We reserve the right to make changes favouring technical progress. 13 ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Pa ALARM EXHAUST: m³h: xxxx Pa: xxxx If activated, pressure alarm data on exhaust side ACTUAL VALUES SUPPLY(1) xxxx m³h Display of actual values 17 SUPPLY(1) xxxx Pa Actual counterpressure on fan 1, supply side 18 SUPPLY2 xxxx m³h If 4000: Actual airflow delivered by fan 2, supply side 19 SUPPLY2 xxxx Pa If 4000: Actual counterpressure on fan 2, supply side 20 EXHAUST(1) xxxx m³h EXHAUST(1) xxxx Pa Actual airflow delivered by fan 1, exhaust side 22 EXHAUST2 xxxx m³h If 4000: Actual airflow delivered by fan 2, exhaust side 23 If 4000: Actual counterpressure on fan 2, exhaust side 24 EXHAUST2 xxxx Pa K1 OPEN 25 K2 xxxxxx 26 K3 OPEN Status of input K2 : OPEN or CLOSED (CA mode), or xx,x V if (LS/CPs) or ‘Not used’ (CPf mode) Status of input K3 : OPEN or CLOSED 27 IN3 OPEN Status of input IN3 : OPEN or CLOSED (selection of master: i/o circuit or RC) 28 IN4 OPEN Status of input IN4 : OPEN or CLOSED (fire alarm) 29 IN5 OPEN Status of input IN5 : OPEN or CLOSED (external pressure alarm device) 30 IN6 OPEN Status of input IN6 : OPEN or CLOSED (post-heating NV option on/off) 31 IN7 OPEN 32 IN8 OPEN Status of input IN7 : OPEN or CLOSED (stop/start the supply fan(s) in case of fire alarm(s) Status of input IN8 : OPEN or CLOSED (Stop/start of the exhaust air fans in case of a fire alarm) 33 T°1 xx,x °C 34 T°2 xx,x °C 35 T°3 xx,x °C Display of the actual value (°C) on sensor S3 (resulting exhaust T° used for antifrost control). 36 T°4 xx,x °C 37 T°5 xx,x °C If NV option (post-heating water): Display of actual value of T° sensor S4 (used for coil antifreeze control). -If NV option: display of value of S5 (used for the T° control system of NV coil with 3 way valve) (compulsory) - If no NV option is used this input can display the actual output T° (option) 38 39 BYPASS CLOSED A-FREEZE OFF 40 OUT1 xx.x V 14 15 16 21 If pressure alarm is activated, display of setup values (m3/h, Pa) at which alarm will be turned on for the exhaust side (CA and LS modes). Actual airflow delivered by fan 1, supply side Actual counterpressure on fan 1, exhaust side Status of input K1 : OPEN or CLOSED Display of the actual value (°C) on sensor S1 (outside T° used for bypass control) Display of the actual value (°C) on sensor S2 (inside T° used for bypass control) Display of by-pass status OPEN or CLOSED Display of status of anti-frosting device of heat exchanger or post-heating coil OFF / REC ON / NV ON. If option NV: Display of output voltage value OUT1 that controls the 3 way valve on NV coil. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 48 Status 03.09.09 We reserve the right to make changes favouring technical progress. 41 CT IN CLOSED 42 R3 SAT3 CBr: OFF 43 R2 SAT3 CBr: OFF Instruction manual 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG If CT option (inlet damper): Display of status of damper : CLOSED / OPENING / OPEN If KW IN option: Display of status of the relay R3 (ON or OFF) of SAT3 mounted on CBr and serial connected on the control panel of the power control of the preheating coil KW IN. If KW OUT option: Display of status of the relay R2 (ON or OFF) of SAT3 mounted on CBr and serial connected on the control panel of the power control of the pre-heating coil KW OUT. © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 49 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Appendix 4: INSTALLATION INSTRUCTIONS NV POSTHEATING COIL To enhance your Maxi with an NV postheating coil you need: 1) 2) 3) 4) 5) Assemble the NV water coil, the 3 ways valve and the T° sensors in the unit Make the water connections Make the electrical connections Configure the new option using the ‘product setup’ menu Configure the assigned output air T° with ‘setup’ menu Maxi unit with NV post heating coil 1 4 3 2 1 = CBr4 TAC3 REC circuit 2 = i/o REC circuit 3 = NV post-heating coil (to be assembled by installer) 4 = 3 ways valve (to be assembled by installer) © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 50 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Step 1: Assemble the NV water coil, the 3 ways valve and the T° sensors in the unit - Fasten one of the 2 T° sensors delivered in the supply ducting (T5 sensor). - Fasten the other sensor on the NV water coil as shown in picture 1. - Assemble the water coil NV in the unit as shown in picture 1. - Fasten the coil as indicated in pictures 2 and 3 hereunder. - Fasten the 3 ways valve in the unit as picture 4 shows. T4 sensor Picture 1: NV coil proper mounting and sensor positioning Picture 2: Fasten lower part of coil as shown. Picture 3: Only lay the upper part of the coil on the frame, do not use fixing materials as this may cause damage to the heat recovery unit. Picture 4: Fasten 3 ways valve in the unit as shown (fastening plates are delivered) © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 51 Status 03.09.09 ® Instruction manual 801 DC - 4001 DC We reserve the right to make changes favouring technical progress. WÄRMERÜCKGEWINNUNG Step 2: Make the water connections • Connection schematic: • Connection specifications: Unit 801 1201 2001 3001 4001 Coil connection Ø 1/2’’ 1/2’’ 1/2’’ 1/2’’ 1/2’’ 3 ways valve connection Ø 3/4’’ 3/4’’ 3/4’’ 3/4’’ 3/4’’ Heating capacity (*) 4,5 kW 8,0 kW 13,2 kW 19,4 kW 27,8 kW Water flow (*) 199 l/h 353 l/h 585 l/h 857 l/h 1200 l/h Water Pressure loss (*) 1,4 kPa 6,5 kPa 20,4 kPa 11,1 kPa 26,8 kPa (*) Nominal values for following conditions: air T° in 18°C, water regime of 90/70°C and maximum airflow. For other selection conditions please refer to Maxi selection program. Step 3: Make the electrical connections 3.1 Connecting the 2 T° sensors (T4 et T5) a) Connect the T° sensor coming from the water coil (T4) to terminals GND and T°4 of the CBr4 TAC3 REC circuit (see page 1). b) Connect the T° sensor coming from the ducting (T5) to terminals GND and T°5 of the i/o TAC3 REC circuit (see page 1). © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 52 Status 03.09.09 We reserve the right to make changes favouring technical progress. ® Instruction manual 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG 3.2 Connecting the 3 ways valve to the control board Make the electrical connection of the valve to the CBr4 TAC3 REC circuit as shown hereunder: 3.3 Connecting your circulator (not provided) to the control (optional) It is possible to connect the control of your circulator to relay O.R.3 of the i/o circuit as shown hereunder: © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 53 Status 03.09.09 Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC ® WÄRMERÜCKGEWINNUNG Step 4: Configure the NV option using the ‘product setup’ menu This setup is done using the LCD display and the SETUP, ↑, ↓ and ENTER keys of the RC. To start configuration: - Press on the selection key of the RC (left on the picture), so that the SETUP LED is lit - Press simultaneously on the ↑ and ↓ until SETUP PRODUCT appears on the screen Principle: select with ↑ and ↓ keys then press ENTER key to validate. Numbers are introduced digit by digit. Step Display Description 1 CODE 0000 REC TYPE xxxxxx PREHEAT KW IN? N/Y POSTHEAT OFF CT IN ? N/Y END SETUP Enter 5030 to enter product setup menu 2 3 4 5 6 Press ENTER do not modify pre-set factory code Press ENTER do not modify pre-set factory code Select NV from list then press ENTER Press ENTER do not modify pre-set factory code End of product setup Step 5. Configure the assigned output T° using the ‘setup’ menu This setup is done using the LCD display and the SETUP, ↑, ↓ and ENTER keys of the RC. To start configuration: - Press on the selection key of the RC (left on the picture), so that the SETUP LED is lit - Press simultaneously on the ↑ and ↓ until SETUP PRODUCT appears on the screen Principle: select with ↑ and ↓ keys then press ENTER key to validate. Numbers are introduced digit by digit. Step Display Description 1 LANGUAGE? GB SUPPLY ? xx°C(NV) WORKING MODE xxx Choose your language 2 3 Enter here the assignment T° to be held constant by the NV coil and its control system. Press the SETUP key to exit setup mode © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 54 Status 03.09.09 ® Instruction manual We reserve the right to make changes favouring technical progress. 801 DC - 4001 DC WÄRMERÜCKGEWINNUNG Appendix 5: INSTALLATION CONTROL DATASHEET (to be filled in after starting the installation) Installed by: Name: ______________________________________________________________________________ Company: ______________________________________________________________________________ Address: ______________________________________________________________________________ Telephone: ______________________________________________________________________________ Installation date: ___/___/___ CONFIGURATION PARAMETERS : 1 model 2 3 Working mode If CA mode: CA LS CPs m³h K1 = Other m³h K2 = m³h K3 = 4 If LS mode: Vmin = Vmax = m³h≡Vmin = m³h≡Vmax = 5 If CPs mode: 6 7 % EXT/PUL Pressure alarm (modes CA / LS only) 8 9 9 If KWin option : If KWout option If NV option : % on K3 = Assignment Pa= V (or % on K3 = % Activated ? yes / no If yes: Automatic / Manual setup Initialisation: Supply: m³h Pa Exhaust: m³h Pa T° KWin = °C T° KWout = °C T° NV = °C Pa) Indicate here all changes made in the advanced setup, if any: VALUES READ OFF DISPLAY WHEN in OPERATION: 1 Supply Aiflow 1 2 Supply pressure 1 3 Supply airflow 2 ( 4000 only) 4 Supply pressure 2 ( 4000 only) 5 Exhaust airflow 1 6 Exhaust pressure 1 7 Exhaust airflow 2 ( 4000 only) 8 Exhaust pressure 2 ( 4000 only) m³/h Pa m³/h Pa m³/h Pa m³/h Pa © Paul Wärmerückgewinnung GmbH • August-Horch-Straße 7 • 08141 Reinsdorf • Deutschland Tel: +49(0)375-303505-0 • Fax: +49(0)375-303505-55 • E-Mail: [email protected] • Internet: www.paul-lueftung.de 55